Neutral Sizing in Harmonic Rich Installations

Both national and international standards for the conductor sizing of cables do not adequately take into account the additional heat load arising from harmonic currents. Some standards prescribe the maximum current values for four-conductor and five-conductor cables under the assumption that only two or three conductors are loaded. However, today’s harmonic situations may give rise to the fourth conductor (neutral) being fully loaded or even overloaded simultaneously with a balanced load on the three phase conductors. Other standards provide a general instruction that under a particular harmonic impact on the phase conductors, a certain additional load has to be taken into account for sizing the neutral conductor. However, the practitioner will usually not know how much harmonic impact arises from a particular load or group of loads.

In the following application note, an approach will be given to estimate the additional thermal impact due to harmonic currents in the LV power supply system of a building. Based on this estimation, it provides a methodology on how to dimension and select three-phase cables that are supposed to feed single-phase final circuits containing distorting loads.

The Highlights from this publication:

  • The harmonic impact on the neutral current can be substantial. Cables have to be over-dimensioned accordingly.
  • Assuming that all harmonics accumulate in the neutral results in an approach that falls on the safe side.
  • It is good to keep this safety margin, because similar loads can have a very different harmonic behaviour.
  • It is also good to provide some reserve for imbalance coming on top of the harmonics.

DOWNLOAD RESOURCES

Application Note - Neutral Sizing in Harmonic Rich Installations

Related POST

High ROI for Industries from Investments in PQ

Industrial end-customers in India use nearly 44% of the electricity produced in the country (accordi..

Read more

Strategies to arrest PQ Problems arising out of LED Lights

How investments in LEDs designed and manufactured with quality parts and adherence to standards can ..

Read more

E$$MEET - Pune on 24th October 2018 at ICC Trade Towers

APQI is happy to invite you for the second E$$MEET - Pune on 24th October 2018 at ICC Trade Towers. ..

Read more

SEEM National Energy Management Awards (SNEMA 2020)

APQI is glad to be associated with SEEM, it's National Support Network (NSN) Partner, as Knowledge P..

Read more

Design for Electrical Safety

Unleashing the limitless possibilities of electricity in technological applications requires proper ..

Read more

Integrated Earthing Systems (Earthing Grid)

Businesses and governments will continue to focus on efficiency and quality improvements while at th..

Read more

7th Webinar How to calculate Electric Losses due to poor PQ?

27th November, 2015 (Thursday) - In our increasingly digital economy, maintaining power quality i..

Read more

14th Webinar - Business case for Loss Reduction using advanced Volt-VAR control in Indian grid

22nd February, 2018 (Thursday) - India's power grid system is massive and needs re-balancing to deal..

Read more
Drop us a message

You're in the right place! Just drop us a message. How can we help?

Or see contact page
There seems to be some problem with validating your request. Please try again.
Thank You! Your message has been delivered.