Neutral Sizing in Harmonic Rich Installations

Both national and international standards for the conductor sizing of cables do not adequately take into account the additional heat load arising from harmonic currents. Some standards prescribe the maximum current values for four-conductor and five-conductor cables under the assumption that only two or three conductors are loaded. However, today’s harmonic situations may give rise to the fourth conductor (neutral) being fully loaded or even overloaded simultaneously with a balanced load on the three phase conductors. Other standards provide a general instruction that under a particular harmonic impact on the phase conductors, a certain additional load has to be taken into account for sizing the neutral conductor. However, the practitioner will usually not know how much harmonic impact arises from a particular load or group of loads.

In the following application note, an approach will be given to estimate the additional thermal impact due to harmonic currents in the LV power supply system of a building. Based on this estimation, it provides a methodology on how to dimension and select three-phase cables that are supposed to feed single-phase final circuits containing distorting loads.

The Highlights from this publication:

  • The harmonic impact on the neutral current can be substantial. Cables have to be over-dimensioned accordingly.
  • Assuming that all harmonics accumulate in the neutral results in an approach that falls on the safe side.
  • It is good to keep this safety margin, because similar loads can have a very different harmonic behaviour.
  • It is also good to provide some reserve for imbalance coming on top of the harmonics.

DOWNLOAD RESOURCES

Application Note - Neutral Sizing in Harmonic Rich Installations

Related POST

Impact of Power Quality on T&D and Power Systems of Different Types

The electricity industry is essential for social & economic development and plays an important role ..

Read more

De Mystifying PQ: Interrelation with Power Supply Reliability, AT&C Losses, Energy Efficiency

The Indian electricity network is undergoing considerable change that is brought about by new techno..

Read more

One Day Conference on Strengthening Green Steel Production: Building Pillars for New India on 24th November, 2017, New Delhi

United Nations Development Programme (UNDP) in partnership with Ministry of Steel (MoS), GoI has bee..

Read more

One Day Seminar On Electrical Power Quality Management By KLN College Of Engineering

KLN College of Engineering announces a one-day seminar on Electrical Power Quality Management for th..

Read more

Severe Voltage Harmonics Distortion in Distribution System

This case study depicts a utility distribution system which was installed decades back to cater to t..

Read more

PLCs Tripping - A Case Study of identification of voltage Disturbance, and solution

The electronic equipments such as PLCs and digital processors are sensitive to power quality related..

Read more

17th Webinar - Regulatory and Policy Landscape around PQ for more resilient grid in 21st Century

12th June, 2018(Tuesday) - India's 21st century electricity grid is becoming smarter with the help o..

Read more

15th Webinar - Impact of distributed Solar Net Metering on grid stability and preparations that DISCOMs can undertake

03rd April, 2018 (Tuesday) India's major dependence on imported fossil fuel for its energy needs is..

Read more
Drop us a message

You're in the right place! Just drop us a message. How can we help?

Or see contact page
There seems to be some problem with validating your request. Please try again.
Thank You! Your message has been delivered.