Neutral Sizing in Harmonic Rich Installations

Both national and international standards for the conductor sizing of cables do not adequately take into account the additional heat load arising from harmonic currents. Some standards prescribe the maximum current values for four-conductor and five-conductor cables under the assumption that only two or three conductors are loaded. However, today’s harmonic situations may give rise to the fourth conductor (neutral) being fully loaded or even overloaded simultaneously with a balanced load on the three phase conductors. Other standards provide a general instruction that under a particular harmonic impact on the phase conductors, a certain additional load has to be taken into account for sizing the neutral conductor. However, the practitioner will usually not know how much harmonic impact arises from a particular load or group of loads.

In the following application note, an approach will be given to estimate the additional thermal impact due to harmonic currents in the LV power supply system of a building. Based on this estimation, it provides a methodology on how to dimension and select three-phase cables that are supposed to feed single-phase final circuits containing distorting loads.

The Highlights from this publication:

  • The harmonic impact on the neutral current can be substantial. Cables have to be over-dimensioned accordingly.
  • Assuming that all harmonics accumulate in the neutral results in an approach that falls on the safe side.
  • It is good to keep this safety margin, because similar loads can have a very different harmonic behaviour.
  • It is also good to provide some reserve for imbalance coming on top of the harmonics.

DOWNLOAD RESOURCES

Application Note - Neutral Sizing in Harmonic Rich Installations

Related POST

Impact of Electric Vehicles on Power Quality

Today energy efficiency is a top priority, boosted by a major concern with climatic changes and by t..

Read more

Total Power Quality Management in an Automotive Component Manufacturing Unit

Delphi-TVS , a joint venture between Delphi Corporation, USA, and T.V. Sundaram Iyengar & Sons, Indi..

Read more

Apqi Hosted It's 17th National Seminar on Total Power Quality Management (Tpqm) At Ludhiana On 25th March (Tuesday) 2014

Asia Power Quality Initiative (APQI) hosted a full day seminar, 17th in its series, on Total Power Q..

Read more

TRAFOCARE 6th Workshop on Transformers held at Mumbai on 07-08 August, 2018

To ensure good Power Quality you need to give your transformer a good environment in order to have e..

Read more

Power Quality Solution through Harmonics Distortion Correction for Corporate Head Office Building

An Indian electricity utility has mandated to limit harmonic distortion starting from the year 2012,..

Read more

Innovative Harmonic Filtering Solution – Sponge Iron Plant

The case study looks into the effect of poor power quality and harmonic distortion resulting in dist..

Read more

18th Webinar - kVAh Billing - the 4 things you must know to optimize energy bills

30th July, 2020(Thursday) - After implementation of the kVAh tariff structure by MSEDCL in April 202..

Read more

19th Webinar - India's Electric Mobility Ambitions - Can Power Quality issues lead to flat tyres?

30th October, 2020 (Friday) - India's speed of adopting Electric Vehicles can be defined but with on..

Read more
Drop us a message

You're in the right place! Just drop us a message. How can we help?

Or see contact page
There seems to be some problem with validating your request. Please try again.
Thank You! Your message has been delivered.