Neutral Sizing in Harmonic Rich Installations

Both national and international standards for the conductor sizing of cables do not adequately take into account the additional heat load arising from harmonic currents. Some standards prescribe the maximum current values for four-conductor and five-conductor cables under the assumption that only two or three conductors are loaded. However, today’s harmonic situations may give rise to the fourth conductor (neutral) being fully loaded or even overloaded simultaneously with a balanced load on the three phase conductors. Other standards provide a general instruction that under a particular harmonic impact on the phase conductors, a certain additional load has to be taken into account for sizing the neutral conductor. However, the practitioner will usually not know how much harmonic impact arises from a particular load or group of loads.

In the following application note, an approach will be given to estimate the additional thermal impact due to harmonic currents in the LV power supply system of a building. Based on this estimation, it provides a methodology on how to dimension and select three-phase cables that are supposed to feed single-phase final circuits containing distorting loads.

The Highlights from this publication:

  • The harmonic impact on the neutral current can be substantial. Cables have to be over-dimensioned accordingly.
  • Assuming that all harmonics accumulate in the neutral results in an approach that falls on the safe side.
  • It is good to keep this safety margin, because similar loads can have a very different harmonic behaviour.
  • It is also good to provide some reserve for imbalance coming on top of the harmonics.

DOWNLOAD RESOURCES

Application Note - Neutral Sizing in Harmonic Rich Installations

Related POST

How Poor Power Quality Can Lead to Electrical Fires?

Going beyond Short Circuits Electrical fires constitute a significant percentage of the total numbe..

Read more

Power Quality (PQ) Issues In VFD

In the automated environment of the modern facilities and equipment, VFDs (also known as Variable Sp..

Read more

Distribution Utility Meet (DUM) on 29-30 November 2017 at Bangalore

India Smart Grid Forum, is facilitating Bangalore Electric Power Supply Company (BESCOM) in bringing..

Read more

One Day Workshop on Power Quality Note for HT Industries, 28th September 2019 at Madurai

The factories of the future have computer-driven systems that are increasingly monitoring physical p..

Read more

Case Study of HT Reactor failure? A Resonance Phenomenon in 11KV Water Pumping Station

A booster pumping station (BPS) in South India with high power HT pumping motors reported sudden fai..

Read more

Modernisation with New Non-Linear Loads and TPP A Cement Industry

Whenever plant undergoes modernization, basically several types of non-linear loads are added newly ..

Read more

14th Webinar - Business case for Loss Reduction using advanced Volt-VAR control in Indian grid

22nd February, 2018 (Thursday) - India's power grid system is massive and needs re-balancing to deal..

Read more

4th Webinar Innovations In PQ Interventions

21st May, 2015 (Thursday) - Power Quality, one of the major issues in electricity distribution s..

Read more
Drop us a message

You're in the right place! Just drop us a message. How can we help?

Or see contact page
There seems to be some problem with validating your request. Please try again.
Thank You! Your message has been delivered.