Neutral Sizing in Harmonic Rich Installations

Both national and international standards for the conductor sizing of cables do not adequately take into account the additional heat load arising from harmonic currents. Some standards prescribe the maximum current values for four-conductor and five-conductor cables under the assumption that only two or three conductors are loaded. However, today’s harmonic situations may give rise to the fourth conductor (neutral) being fully loaded or even overloaded simultaneously with a balanced load on the three phase conductors. Other standards provide a general instruction that under a particular harmonic impact on the phase conductors, a certain additional load has to be taken into account for sizing the neutral conductor. However, the practitioner will usually not know how much harmonic impact arises from a particular load or group of loads.

In the following application note, an approach will be given to estimate the additional thermal impact due to harmonic currents in the LV power supply system of a building. Based on this estimation, it provides a methodology on how to dimension and select three-phase cables that are supposed to feed single-phase final circuits containing distorting loads.

The Highlights from this publication:

  • The harmonic impact on the neutral current can be substantial. Cables have to be over-dimensioned accordingly.
  • Assuming that all harmonics accumulate in the neutral results in an approach that falls on the safe side.
  • It is good to keep this safety margin, because similar loads can have a very different harmonic behaviour.
  • It is also good to provide some reserve for imbalance coming on top of the harmonics.

DOWNLOAD RESOURCES

Application Note - Neutral Sizing in Harmonic Rich Installations

Related POST

Greenfield Design and Predictive Maintenance Two keys to achieve Power Quality

Power Quality (PQ) is often characterised as the electrical network's ability to supply a clean and ..

Read more

Unlocking the value in the volume of PQ Data

PQ Data, whether its voltage disturbances, current unbalance or any such other critical parameter, i..

Read more

IUKAN Annual Conference 2015

Typical utility projects in India are characterized by a wide geographical spread and broad demograp..

Read more

CAPACIT 2019- 9th International Conference on Capacitors

CAPACIT Conference which is held once in four years provides a common and a unique platform to all t..

Read more

The Right Selection UPS & Harmonics

Uninterruptible Power Supply or commonly known as UPS, thought to be designed for emergency power su..

Read more

Power Quality in the IT. ITES. Data Center

Availability of reliable electrical power with good quality is one of the governing aspects of produ..

Read more

12th Webinar Manage your assets downtime through better understanding of PQ Issues

05th October, 2017 (Thursday) - In today's uncertain economic climate, capital and operational bud..

Read more

4th Webinar Innovations In PQ Interventions

21st May, 2015 (Thursday) - Power Quality, one of the major issues in electricity distribution s..

Read more
Drop us a message

You're in the right place! Just drop us a message. How can we help?

Or see contact page
There seems to be some problem with validating your request. Please try again.
Thank You! Your message has been delivered.