Neutral Sizing in Harmonic Rich Installations

Both national and international standards for the conductor sizing of cables do not adequately take into account the additional heat load arising from harmonic currents. Some standards prescribe the maximum current values for four-conductor and five-conductor cables under the assumption that only two or three conductors are loaded. However, today’s harmonic situations may give rise to the fourth conductor (neutral) being fully loaded or even overloaded simultaneously with a balanced load on the three phase conductors. Other standards provide a general instruction that under a particular harmonic impact on the phase conductors, a certain additional load has to be taken into account for sizing the neutral conductor. However, the practitioner will usually not know how much harmonic impact arises from a particular load or group of loads.

In the following application note, an approach will be given to estimate the additional thermal impact due to harmonic currents in the LV power supply system of a building. Based on this estimation, it provides a methodology on how to dimension and select three-phase cables that are supposed to feed single-phase final circuits containing distorting loads.

The Highlights from this publication:

  • The harmonic impact on the neutral current can be substantial. Cables have to be over-dimensioned accordingly.
  • Assuming that all harmonics accumulate in the neutral results in an approach that falls on the safe side.
  • It is good to keep this safety margin, because similar loads can have a very different harmonic behaviour.
  • It is also good to provide some reserve for imbalance coming on top of the harmonics.

DOWNLOAD RESOURCES

Application Note - Neutral Sizing in Harmonic Rich Installations

Related POST

Power Quality and Energy Efficiency as Least Cost Planning (LCP) in Utilities Planning

Planning is one of the most important aspect of running a business efficiently. Planning can address..

Read more

Smart Meters A New Window of Possibility In Improving PQ?

Advanced Metering Infrastructure (AMI) projects enabled by Smart Meters are set to revolutionize ele..

Read more

Interactive Workshop on Power Quality and Harmonics at Pune

APQI and MSEDCL jointly hosted a full day interactive workshop on Harmonics and Power Quality at Pun..

Read more

Apqi Vietnam Partner Meeting 2013 & PQ Handbook Workshop

APQI – Vietnam Chapter held it’s annual partner meeting 2013 and PQ handbook workshop respectively a..

Read more

Solutions to PQ Issues in a Chemical Industry

Debilitating effect on electrical system components due to high level of harmonics and consequent ..

Read more

Solutions for Non-linear loads of a weld shop: A case study from an automobile industry

A weld shop forms a larger component of non-linear load in any large sized modern automobile industr..

Read more

10th Webinar Assessing Transformer Loss in Harmonics High Environment

17th November, 2016 (Thursday) - Transformers are one of the most important and high CAPEX assets..

Read more

6th Webinar Measurement and Verification of Power Quality in Utilities

24th September, 2015 (Thursday) - Power quality (PQ) in the low voltage (LV) and Medium Voltage ..

Read more
Drop us a message

You're in the right place! Just drop us a message. How can we help?

Or see contact page
There seems to be some problem with validating your request. Please try again.
Thank You! Your message has been delivered.