Nuisance Tripping of Circuit Breakers (True RMS Measurements)

Nuisance tripping of circuit breakers is a common problem in many commercial and industrial installations. This Application Note explains the need to use true RMS measurement instruments when troubleshooting and analyzing the performance of a power system.

Nuisance tripping of circuit breakers is often caused by the load current being distorted by the presence of harmonic currents drawn by non-linear loads. Harmonic currents distort the current waveform and increase the load current required to deliver energy to the load. Many measurement instruments, even quite modern ones, use an averaging measurement technique that does not measure harmonic currents correctly. The readings may be as much as 40% too low, and circuit breakers and cable sizes may be underrated as a result.

True RMS meters, which take the complete distorted waveform into account, should be used instead.

Application Note Author & Publisher: Leonardo ENERGY

Source files for this application note

Related POST

Integrating Power Quality (PQ) Management In Building Management Systems (IBMS) For Better Impact

An assessment of how better PQ management in facilities that use Intelligent Building Management Sys..

Read more

Business Case for PQ Investment by Commercial Buildings

According to total electricity sales (as per 2011-12), around 54% of the energy produced in India is..

Read more

POWERMAX 2017

The One and Only international events in the center of Business and Busiest city" Jakarta would be h..

Read more

CIPPE The 8th China International Petrochemical Technology and Equipment Exhibition

The 8th China (Shanghai) International (abbr. cippe 2016 Shanghai), will take place with China Inter..

Read more

Integrated Earthing Systems (Earthing Grid)

Businesses and governments will continue to focus on efficiency and quality improvements while at th..

Read more

Polypropylene Plant Expansion of Drives

The DC drives with six-pulse rectifier, generate significant 5th and 7th harmonics and appear as a s..

Read more

1st Webinar Business Case For Power Quality Investments By Indian Power Distribution Utilities

17 June, 2014 (Thursday) - Loss reduction, one of the foremost Business performance metrics, drive..

Read more

19th Webinar - India's Electric Mobility Ambitions - Can Power Quality issues lead to flat tyres?

30th October, 2020 (Friday) - India's speed of adopting Electric Vehicles can be defined but with on..

Read more
Drop us a message

You're in the right place! Just drop us a message. How can we help?

Or see contact page
There seems to be some problem with validating your request. Please try again.
Thank You! Your message has been delivered.